Calculate pressure loss for low pressure air circular and rectangular ducts using the Moody diagram.
The calculators use the Darcy-Weisbach pressure loss equation. For low Reynolds numbers Re < 2000, the fluid flow is laminar and the Darcy friction factor should be calculated using the Hagen-Poiseuille laminar flow equation. For high Reynolds numbers Re > 4000, the fluid flow is turbulent and the Darcy friction factor should be calculated using one of the turbulent flow equations. In the transition region 2000 < Re < 4000, the flow is unstable and the friction loss cannot be reliably calculated.
Minor losses can be entered as either a K friction factor, a length, or length over diameter ratio. The minor losses are used to account for pipeline fittings such as bends, tees, valves etc.. :sg:For air the gas specific gravity SG = 1.0. For low pressure air the compressibility factor is assumed equal to one.
Change Module :